Skip to main content
Siemens 3RV1031-4HB10

Siemens 3RV1031-4HB10 SIRIUS Motor Protection Circuit Breake

MPN 3RV1031-4HB10

Siemens SIRIUS, motor protection circuit breaker, 3RV1031-4HB10, 50 A continuous, 22 kW at 400 V, CLASS 20, 3-pole, screw terminals, IP20 front.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RV1031-4HB10 specifications
ParameterValue
Depth149 mm
Width55 mm
Height140 mm
Trip classCLASS 20

Product details

The Siemens 3RV1031-4HB10 is a SIRIUS motor-protection circuit breaker rated for 50 A continuous current and 22 kW at 400 V, with a CLASS 20 trip characteristic. That CLASS 20 curve allows the breaker to ride through the high inrush of a standard induction motor start (typically 6–8× FLA for 10–20 seconds) without nuisance tripping, while still protecting against locked-rotor and overload conditions. The 50 A continuous rating and 22 kW at 400 V mean it is sized for a motor load up to that power — a 30 hp (22 kW) four-pole motor at 400 V draws roughly 42–45 A full-load, so the 50 A frame gives headroom for ambient derating or a slightly oversized motor.

Short-circuit coordination — what the SCCR ratings mean for panel design

This breaker carries a 100 kA interrupting rating at 240 V AC, 50 kA at 400 V, 10 kA at 500 V, and 4 kA at 690 V. The breaker also includes phase failure detection, which trips on loss of one phase — a common cause of single-phasing motor damage that a standard thermal overload might miss.

Mounting and integration — DIN rail fit, wiring, and clearances

Width is 55 mm, height 140 mm, depth 149 mm. No side clearance required (0 mm backwards and at the side), so you can pack breakers tight on the rail. Main circuit terminals accept solid 2x (0.75…16 mm²) or stranded 2x (0.75…25 mm²) and 1x (0.75…35 mm²). Auxiliary and control circuit terminals are screw-type.

MPN
3RV1031-4HB10