Skip to main content
Siemens 3RV1421-1EA10

Siemens 3RV1421-1EA10 SIRIUS Circuit Breaker, 4 A, 100 kA at

MPN 3RV1421-1EA10

Siemens SIRIUS 3RV1421-1EA10, circuit breaker for transformer protection, 3-pole, 4 A, 100 kA at 400 V AC, Trip Class 10, screw terminals, DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RV1421-1EA10 specifications
ParameterValue
Depth96 mm
Width45 mm
Height97 mm
Trip classCLASS 10

Product details

Transformer-protection circuit breaker, 4 A, 100 kA

The 3-pole unit carries a Trip Class 10 characteristic, meaning it trips within 10 seconds at 7.2× rated current — fast enough to protect a transformer winding from sustained overload while riding through inrush.

Main and auxiliary/control circuits both use screw-type terminals; solid wire accepted is 2× (1 … 2.5 mm²) and 2× (2.5 … 6 mm²), with the same ranges for stranded and finely stranded with ferrule. AWG equivalents are 2× (14 … 10). Backwards clearance is 0 mm — no extra space needed behind the rail.

Breaking capacity across voltage

Breaking capacity is 100 kA at 240 V AC, 100 kA at 400 V AC, 100 kA at 500 V AC, and 6 kA at 690 V AC. For most 400 V distribution panels the full 100 kA is available, which covers high-fault installations downstream of large transformers.