Skip to main content
Siemens 3RW5214-1TC05

Siemens 3RW5214-1TC05 SIRIUS Soft Starter, 200-600 V

MPN 3RW5214-1TC05
Active

Siemens SIRIUS 3RW5214-1TC05 soft starter, 200-600 V control supply, Class 10A / 10E / 20E trip, PROFIBUS/Modbus/EtherNet/IP/PROFINET, UL/CSA/CE, current production.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RW5214-1TC05 specifications
ParameterValue
Mountingscrew fixing
Depth152 mm
Width170 mm
Height275 mm
Trip classCLASS 10 A (default) / 10E / 20E; acc. to IEC 60947-4-2
Service factor1

Product details

Trip class and motor protection — the number that decides the start

The 3RW5214-1TC05: That's the standard for most pump, fan, and compressor starts where the load accelerates in 5–8 seconds. The wider class doesn't change the hardware; it's a firmware setting. The minimum settable motor current is 7.5 A, and the minimum load is 15% of that value — so don't try to soft-start a 2 A motor on this frame. The current sensing resolution won't give you reliable protection below about 1.1 A.

Fieldbus support — one part, five networks

This soft starter carries PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET on board — no external gateway module needed. The PROFINET variant also supports PROFIenergy for coordinated energy management across the line. The control supply voltage range is 200–600 V, so it runs directly from the same line voltage as the motor — no control transformer required. That simplifies panel wiring for multi-voltage plants running 208 V in one area and 480 V in another.

Application features — pump ramp down and soft torque

Pump Ramp Down gradually reduces torque on shutdown instead of coasting, which eliminates water hammer in long pipe runs. Soft Torque reduces mechanical shock on geared or belt-driven loads during the start ramp. At 50 °C expect roughly a 10% derating; at 60 °C it's about 20%. Mounting position allows ±10° rotation and forward/backward tilt on a vertical surface.

Approvals and compliance — UL, CSA, CE on the nameplate

The 3RW5214-1TC05 carries CE marking for the European market, UL approval for North America, and CSA approval for Canada. No separate certification paperwork is needed for most panel builds — the nameplate covers it. The service factor is 1.0, meaning no overload margin beyond the set current. If your motor has a 1.15 SF, you still set the starter to the motor nameplate FLA — the starter's protection curve does not follow the motor's SF.

This is a current-production part (lifecycle stage: current). It's sourced through authorized Siemens distribution and quoted against your BOM quantity. No last-time-buy or obsolescence risk on the horizon. Mounting is screw-fixed to the panel or DIN rail, with 100 mm clearance above and 75 mm below for airflow.

MPN