Siemens 3RW5214-1TC05 SIRIUS Soft Starter, 200-600 V

MPN3RW5214-1TC05
Active

Siemens SIRIUS 3RW5214-1TC05 soft starter, 200-600 V control supply, Class 10A / 10E / 20E trip, PROFIBUS/Modbus/EtherNet/IP/PROFINET, UL/CSA/CE, current production.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RW5214-1TC05 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS
3RW5214-1TC05 — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)7.5 kW
Rated motor power at 230 V (40 °C)4 kW
Rated operational current at 40 °C31.5 A
Rated operational current at 50 °C28 A
Rated operational current at 60 °C23.9 A
Rated insulation voltage600 V
Minimum settable current (% of Ie)15 %; Relative to smallest settable Ie
Power loss during startup (50 °C)241 W
3RW5214-1TC05 — Control & Connection
ParameterValue
Control supply voltage typeAC/DC
Rated voltage at 50 Hz24 V
Rated voltage at 60 Hz24 V
Main circuit terminal typescrew-type terminals
Control circuit wire range, solid1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
Control circuit wire range, finely stranded (with ferrule)1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
Analog outputNo
Auxiliary contact rated current, AC-15 at 250 V3 A
Auxiliary contact rating (UL)R300-B300
Control supply voltage tolerance, AC 50 Hz (max.)20 %
Control supply voltage tolerance, AC 50 Hz (min.)-20 %
Control supply voltage tolerance, AC 60 Hz (max.)20 %
Control supply voltage tolerance, AC 60 Hz (min.)-20 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
Operating voltage tolerance, inside-delta (max.)10 %
Operating voltage tolerance, inside-delta (min.)-15 %
3RW5214-1TC05 — Protection & Features
ParameterValue
Motor overload protectionYes; Full motor protection (thermistor motor protection and electronic motor overload protection)
Thermistor motor protectionYes; Type A PTC or Klixon / Thermoclick
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2
3RW5214-1TC05 — Mechanical
ParameterValue
Height275 mm
Width170 mm
Depth152 mm
Weight2.1 kg
Mounting position+/- 10° rotation possible and can be tilted forward or backward on vertical mounting surface
Fastening methodscrew fixing
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm
3RW5214-1TC05 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude5 000 m; Derating as of 1000 m, see catalog
Ambient class during operation (IEC 60721)3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)
3RW5214-1TC05 — Specifications
ParameterValue
Trip ClassCLASS 10A (default) / 10E / 20E; acc. to IEC 60947-4-2
Number Of Controlled Phases3
Utilization category according to IEC 60947-4-2AC 53a
Product Feature Integrated Bypass Contact SystemYes
Start-Up Ramp Time Of Soft Starter0 ... 20 s
3RW5214-1TC05 — Electrical
ParameterValue
Current Limiting Value [%] Adjustable130 ... 700 %
Starting Voltage [%]30 ... 100 %
Stopping Voltage [%]50 %; non-adjustable

Product details

Trip class and motor protection — the number that decides the start

The 3RW5214-1TC05: That's the standard for most pump, fan, and compressor starts where the load accelerates in 5–8 seconds. The wider class doesn't change the hardware; it's a firmware setting. The minimum settable motor current is 7.5 A, and the minimum load is 15% of that value — so don't try to soft-start a 2 A motor on this frame. The current sensing resolution won't give you reliable protection below about 1.1 A.

Fieldbus support — one part, five networks

This soft starter carries PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET on board — no external gateway module needed. The PROFINET variant also supports PROFIenergy for coordinated energy management across the line. The control supply voltage range is 200–600 V, so it runs directly from the same line voltage as the motor — no control transformer required. That simplifies panel wiring for multi-voltage plants running 208 V in one area and 480 V in another.

Application features — pump ramp down and soft torque

Pump Ramp Down gradually reduces torque on shutdown instead of coasting, which eliminates water hammer in long pipe runs. Soft Torque reduces mechanical shock on geared or belt-driven loads during the start ramp. At 50 °C expect roughly a 10% derating; at 60 °C it's about 20%. Mounting position allows ±10° rotation and forward/backward tilt on a vertical surface.

Approvals and compliance — UL, CSA, CE on the nameplate

The 3RW5214-1TC05 carries CE marking for the European market, UL approval for North America, and CSA approval for Canada. No separate certification paperwork is needed for most panel builds — the nameplate covers it. The service factor is 1.0, meaning no overload margin beyond the set current. If your motor has a 1.15 SF, you still set the starter to the motor nameplate FLA — the starter's protection curve does not follow the motor's SF.

This is a current-production part (lifecycle stage: current). It's sourced through authorized Siemens distribution and quoted against your BOM quantity. No last-time-buy or obsolescence risk on the horizon. Mounting is screw-fixed to the panel or DIN rail, with 100 mm clearance above and 75 mm below for airflow.

Frequently asked questions

What is the trip class and how do I change it?

The default trip class is Class 10A per IEC 60947-4-2. You can set it to Class 10E or Class 20E via the parameter menu — no hardware change required.

What fieldbus networks does the 3RW5214-1TC05 support?

It supports PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET with PROFIenergy. No external gateway is needed for any of these protocols.

What is the minimum motor current this soft starter can handle?

The minimum settable motor current is 7.5 A, and the minimum load is 15% of that value. For reliable current sensing and protection, don't use it on motors below about 1.1 A FLA.

Does the 3RW5214-1TC05 have UL and CSA approvals?

Yes — it carries CE marking, UL approval, and CSA approval. The nameplate covers all three certifications, so no separate documentation is needed for most panel builds.