Skip to main content
Siemens 3RW5215-3TC14

Siemens 3RW5215-3TC14 Soft Starter, 200-480 V, 11.5 A

MPN 3RW5215-3TC14
Active

Siemens 3RW5215-3TC14 soft starter, hybrid switching device, 200-480 V, 11.5 A minimum, Trip Class 10A/10E/20E, 275 x 170 x 152 mm, screw fixing, PROFIBUS/Modbus/EtherNet/IP/PROFINET.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RW5215-3TC14 specifications
ParameterValue
Mountingscrew fixing
Depth152 mm
Width170 mm
Height275 mm
Trip classCLASS 10 A (default) / 10E / 20E; acc. to IEC 60947-4-2
Service factor1

Product details

Panel fit and ventilation clearance

The 3RW5215-3TC14 measures 275 mm high by 170 mm wide by 152 mm deep. Screw fixing to the backplate is the standard mount; the mounting surface can tilt +/-10° from vertical. Ventilation gaps are mandatory: 100 mm above, 75 mm below, 10 mm forward, 5 mm to the side, and 0 mm backward. Without these clearances, the internal heatsink cannot shed the IGBT losses and the unit derates prematurely. Shock tolerance is 15 g / 11 ms.

Motor protection and trip class

Trip Class 10A is the default setting per IEC 60947-4-2, with selectable 10E and 20E profiles. Minimum settable current is 11.5 A, which sets the lower bound of the motor FLA it can protect. The minimum load is 15 % of the smallest settable Ie.

Fieldbus and control integration

The 3RW5215-3TC14 supports PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET. PROFIenergy is available with the PROFINET communication module. Firmware updates are supported in the field. An error logbook is accessible with special accessories. Auto-reset and remote reset by cycling the control supply voltage are standard.

Wiring terminals and power connections

Solid wire terminations accept two conductors per clamp: 1.0...2.5 mm² for control circuits, and 2.5...10 mm² for the main power path. Rated supply voltage is 200...480 V at 50/60 Hz.

Approvals and compliance documentation

The product category is hybrid switching devices.

MPN
3RW5215-3TC14