Skip to main content
Siemens 3RW5217-3TC14

Siemens 3RW5217-3TC14 Soft Starter, 200-480V, 15.5A

MPN 3RW5217-3TC14
Active

Siemens 3RW5217-3TC14 hybrid soft starter, 200-480 V AC, 15.5 A minimum, Trip Class 10A/10E/20E, PROFIBUS/Modbus RTU/Modbus TCP/EtherNet/IP/PROFINET, screw fixing, 275 x 170 x 152 mm.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RW5217-3TC14 specifications
ParameterValue
Mountingscrew fixing
Depth152 mm
Width170 mm
Height275 mm
Trip classCLASS 10 A (default) / 10E / 20E; acc. to IEC 60947-4-2
Service factor1

Product details

Trip class, voltage window, and what they govern

The 3RW5217-3TC14: Trip Class 10A (default), 10E, or 20E per IEC 60947-4-2. Class 10A means the starter disconnects within 10 seconds of a locked-rotor condition at 7.2× rated current — the right choice for standard induction motors that accelerate quickly. Rated operating voltage is 200-480 V AC, covering the common global low-voltage motor distribution: 200 V, 230 V, 400 V, and 480 V networks.

Fieldbus integration — PROFIBUS, Modbus, and industrial Ethernet

Onboard PROFIBUS DP and Modbus RTU (RS-485) are standard. Modbus TCP, EtherNet/IP, and PROFINET are supported via the PROFINET standard communication module, enabling direct connection to Siemens S7, Rockwell ControlLogix, and third-party PLCs without a gateway. PROFIenergy is available in connection with the PROFINET module, allowing the starter to coordinate energy-saving pauses with the controller during non-production intervals.

Mounting, clearances, and panel fit

Screw fixing (not DIN-rail snap-on). Dimensions: 275 mm height × 170 mm width × 152 mm depth. Minimum clearance around the unit: 100 mm above, 75 mm below, 10 mm forward, 5 mm at the sides, and 0 mm backward — essential for natural convection cooling. Mounting position: vertical surface with ±90° rotation and ±22.5° tilt forward/backward — allows panel orientation flexibility without derating, provided the clearance zones are respected.

Operating temperature and derating threshold

Ambient operating range is -25 °C to +60 °C, with a derating trigger at 40 °C and above. For continuous duty above 40 °C ambient, the output current must be reduced per the derating curve; at 60 °C the usable current is significantly lower than the nominal rating.

Application features — soft torque, pump ramp, and reset modes

Soft Torque and Pump Ramp Down are built in — the ramp-down profile reduces water hammer in pump systems by extending the deceleration time. Remote reset is supported by cycling the control supply voltage; auto-reset is also available.

MPN
3RW5217-3TC14