Siemens SIRIUS 3RW5246-6AC04 soft starter, 160 A minimum, 200-480 V, Class 10A/10E/20E, PROFIBUS, Modbus RTU/TCP, EtherNet/IP, PROFINET, screw fixing, 203 mm depth, 210 mm width, 393 mm height.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RW5246-6AC04 specifications
ParameterValue
Mountingscrew fixing
Depth203 mm
Width210 mm
Height393 mm
Trip classCLASS 10 A (default) / 10E / 20E; acc. to IEC 60947-4-2
Service factor1
Digital output version2 normally-open contacts (NO) / 1 changeover contact (CO)

Product details

Motor current and trip class — what they mean for the line

The 3RW5246-6AC04: The 160 A minimum setting (relative to the smallest settable Ie) means this soft starter is sized for motors drawing at least that current at full load — below that, the starting ramp may not engage the thyristor firing angle correctly, and the overload protection won't coordinate with the motor thermal curve. Trip class is selectable between CLASS 10A (default), 10E, or 20E per IEC 60947-4-2. The voltage range is 200–480 V, covering common global low-voltage networks (208 V, 230 V, 400 V, 480 V). Confirm the line voltage falls within this window — the soft starter's phase-angle firing control needs the full range to maintain torque linearity.

Mounting and panel fit — screw fixing with clearance rules

Screw fixing is the only fastening method — no DIN-rail clip. The unit measures 203 mm deep, 210 mm wide, and 393 mm high. Plan the backplate layout with these dimensions plus the required clearances: 100 mm upwards, 10 mm forwards, 0 mm backwards, 75 mm downwards, and 5 mm at the side. The 0 mm backwards clearance means the unit can sit flush against the back panel, but the 100 mm upward gap is mandatory for airflow and cable bending radius. Mounting position allows a vertical surface with ±90° rotation and ±22.5° tilt front-to-back.

Fieldbus connectivity and control features

Built-in fieldbus support includes PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET (with PROFINET standard communication module). This covers most common automation networks — no external gateway needed for integration into Siemens S7, Rockwell ControlLogix, or Modbus-based systems. Additional control features include soft torque for gentle starts on conveyors, pump ramp down to prevent water hammer, auto-reset and remote reset (by cycling the 24 V control supply), and an analog output configurable as 4–20 mA or 0–10 V via the High Feature HMI. The error logbook is available only with special accessories.

Lifecycle and compliance — active production, global approvals

Approvals include CE marking, UL approval, and CSA approval. Pollution degree 3 per IEC 60947-4-2 means it's rated for industrial environments with conductive pollution — no additional conformal coating required for typical panel conditions.