Siemens SIRIUS 3RW5246-6TC14 soft starter, 160 A minimum, 200-480 V, Class 10A/10E/20E trip, PROFIBUS/Modbus RTU/Modbus TCP/EtherNet/IP/PROFINET, 393 x 210 x 203 mm.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RW5246-6TC14 specifications
ParameterValue
Mountingscrew fixing
Depth203 mm
Width210 mm
Height393 mm
Trip classCLASS 10 A (default) / 10E / 20E; acc. to IEC 60947-4-2
Service factor1
Digital output version2 normally-open contacts (NO) / 1 changeover contact (CO)

Product details

Motor starting duty and trip class selection

The 3RW5246-6TC14 is a SIRIUS hybrid switching device rated for a minimum motor current of 160 A at a supply voltage range of 200 to 480 V. The trip class is configurable as CLASS 10A (default), 10E, or 20E per IEC 60947-4-2, which governs the allowable thermal overload during acceleration. For a high-inertia load like a centrifuge or large fan, selecting CLASS 20E extends the start time window without nuisance tripping; CLASS 10A is the standard for most pump and conveyor starts. The unit supports soft torque and pump ramp down, which reduces mechanical shock on the load train during start and stop. This is relevant for applications where water hammer or belt stress is a failure mode.

Fieldbus integration and communication options

This soft starter ships with onboard PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET standard communication. PROFIenergy is supported when used with the PROFINET communication module, enabling energy management during idle phases. The device also supports firmware updates in the field. No analog output is present, so closed-loop torque control is not available. The remote reset function is triggered by cycling the control supply voltage.

Panel fit and mounting clearances

Dimensions are 393 mm height, 210 mm width, and 203 mm depth. Required clearances: 100 mm upwards, 75 mm downwards, 10 mm forwards, 5 mm at the side, and 0 mm backwards. Shock resistance is 15 g for 11 ms, with potential contact lifting at 12 g for 11 ms.

Regulatory approvals and compliance documentation

The 3RW5246-6TC14 carries CE marking, UL approval, and CSA approval. Service factor is 1.0. The minimum load is 15% relative to the smallest settable Ie.