Skip to main content
Siemens 3RW5515-1HA04

Siemens 3RW5515-1HA04 Soft Starter, 200-480V, Active

MPN 3RW5515-1HA04
Active

Siemens 3RW5515-1HA04 soft starter, 200-480 V rated, Trip Class 10A/10E/20E/30E per IEC 60947-4-2, ATEX/IECEx certified, active production.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RW5515-1HA04 specifications
ParameterValue
Mountingscrew fixing
Depth152 mm
Width170 mm
Height275 mm
Trip classCLASS 10 A / 10E (default) / 20E / 30E; acc. to IEC 60947-4-2
Service factor1.15

Product details

Active production, 200-480 V, ATEX-rated

The 3RW5515-1HA04: Rated for 200-480 V supply, this soft starter covers the common low-voltage motor range across North America and Europe. The wide voltage window means it handles 208 V, 230 V, 400 V, and 480 V without a rewire — just set the motor nameplate parameters during commissioning. ATEX and IECEx certification (both Yes) means it's listed for use in potentially explosive atmospheres — not just a general-purpose box. That's a hard requirement for chemical plants, grain elevators, paint lines, and any Zone-classified area. The cert covers the soft starter itself, not just the enclosure.

Trip Class 10A/10E/20E/30E — what that means for your motor

Trip Class 10A (default) means the soft starter disconnects within 10 seconds at locked-rotor current — that's the standard for most general-purpose pumps and fans. Class 10E is a tighter thermal model for European-rated motors. The selector is parameterizable, so you tune it to the load, not the other way around. Voltage ramp, torque control, pump ramp down, and breakaway pulse are all built in — no add-on cards needed. The breakaway pulse is useful for sticky loads like conveyors that need a short torque hit to break static friction before the ramp takes over. DC braking and combined braking are both present — so if the motor needs to stop faster than coast-to-rest, the soft starter can inject DC into the windings. That's a feature normally found on VFDs, not soft starters, and it saves an external braking contactor.

Fieldbus and panel integration

PROFIBUS, Modbus RTU, Modbus TCP, and EtherNet/IP are all on the menu — no separate gateway needed for most plant networks. PROFIenergy is supported when paired with a PROFINET communication module, useful for energy-aware production scheduling. The 170 mm width and 275 mm height fit a standard 600 mm-wide panel section. Depth is 152 mm, so it clears a 200 mm deep enclosure with room for wiring ducts. Clearance requirements: 100 mm above, 75 mm below, 10 mm in front, 5 mm at the sides — plan the gland plate and DIN rail layout accordingly. Screw terminals for power wiring: dual terminals accept 1.0-2.5 mm² and 2.5-10 mm² — that covers control wiring and motor leads up to about 8 AWG. The analog output is configurable as 4-20 mA or 0-10 V, so it can feed a remote SCADA or panel meter with motor current or torque signal.

Approvals and compliance documentation

No separate agency review needed for most panel builds. Accuracy Class 5 per IEC 61557-12 means the built-in current measurement is within 5 % — good enough for motor protection and energy monitoring without an external CT. The event list, error logbook, and trace function give you diagnostics for commissioning and fault finding without a laptop. Firmware updates are supported in the field — so if Siemens releases a new feature or a bug fix, you can flash it without swapping the hardware. The service factor is 1.15, meaning the soft starter can handle 115 % of rated current continuously — useful for motors running near full load in hot environments.

MPN
3RW5515-1HA04