Skip to main content
Siemens 3RW5552-6HA14

Siemens 3RW5552-6HA14 Soft Starter, 200-480 V, ATEX, Active

MPN 3RW5552-6HA14
Active

Siemens 3RW5552-6HA14 soft starter, 200-480 V, trip class 10A/10E/20E/30E, ATEX/IECEx, PROFIBUS/Modbus/EtherNet/IP, 241×478×764 mm.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RW5552-6HA14 specifications
ParameterValue
Mountingscrew fixing
Depth241 mm
Width478 mm
Height764 mm
Trip classCLASS 10 A / 10E (default) / 20E / 30E; acc. to IEC 60947-4-2
Service factor1.15
Digital output version3 normally-open contacts (NO) / 1 changeover contact (CO)

Product details

Motor protection and trip class selection

The 3RW5552-6HA14 offers selectable trip classes — CLASS 10A / 10E (default) / 20E / 30E — per IEC 60947-4-2, letting you match the thermal overload curve to the motor start profile. CLASS 10A is the tightest, suitable for normal starts;. Rated voltage is 200-480 V, covering standard low-voltage three-phase supplies across 50/60 Hz installations.

Fieldbus and control integration

Built-in support for PROFIBUS, Modbus RTU, Modbus TCP, and EtherNet/IP means this unit drops into most common industrial networks without an extra gateway. PROFINET with PROFIenergy is available via optional communication modules. Analog output configurable as 4-20 mA or 0-10 V for feeding motor current or torque to a PLC or panel meter. The accuracy class is 5 per IEC 61557-12, sufficient for monitoring and trending.

Advanced motor control functions

Includes voltage ramp start, pump ramp down (to reduce water hammer), torque control, breakaway pulse for sticky loads, and DC braking. These are parameterizable via the onboard interface or fieldbus. Service factor 1.15 allows continuous overload above nameplate rating — useful when the motor is oversized for the load. The unit also logs events and errors in a logbook, with a trace function for diagnosing start-up issues.

ATEX and hazardous area compliance

ATEX and IECEx certified (both marked Yes), meaning the soft starter is approved for use in explosive atmospheres — typically Zone 2 or Zone 22, depending on the installation. This is a key differentiator for chemical, oil/gas, and grain-handling applications. UL and CSA approvals are also present, covering North American installations. CE marking confirms conformity with EU directives.

Physical footprint and panel layout

Dimensions: 764 mm high, 478 mm wide, 241 mm deep — a substantial enclosure that needs a dedicated backplate or floor-mount. Clearance requirements: 100 mm above, 75 mm below, 10 mm in front, 5 mm at the sides, and 0 mm behind (panel-mount). Termination is via screw terminals — no special tooling needed for wiring. The unit supports firmware updates in the field, so you can apply later software revisions without swapping hardware.

MPN
3RW5552-6HA14