Skip to main content
Siemens 3RW5553-6HA14

Siemens 3RW5553-6HA14 Soft Starter, 200-480 V, ATEX, Active

MPN 3RW5553-6HA14
Active

Siemens 3RW5553-6HA14 soft starter, 200-480 V AC, ATEX/IECEx certified, trip class 10A/10E/20E/30E, 764 x 478 x 241 mm, screw terminals, active production.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RW5553-6HA14 specifications
ParameterValue
Mountingscrew fixing
Depth241 mm
Width478 mm
Height764 mm
Trip classCLASS 10 A / 10E (default) / 20E / 30E; acc. to IEC 60947-4-2
Service factor1.15
Digital output version3 normally-open contacts (NO) / 1 changeover contact (CO)

Product details

Motor starting in hazardous zones

The 3RW5553-6HA14 carries both ATEX and IECEx certification, making it suitable for soft-starting motors in classified areas — gas or dust zones where a standard starter would require an external isolation barrier.

Trip class and starting profile flexibility

Trip class is field-configurable from CLASS 10A (fast trip for light-start loads) through CLASS 30E (extended ramp for high-inertia loads), per IEC 60947-4-2 — the same standard that governs contactor/motor-starter coordination. Built-in torque control, voltage ramp, and pump ramp-down let you tune the start profile for centrifugal pumps, conveyors, or crushers without an external PLC. A breakaway pulse option handles stuck loads — the starter delivers a short torque spike before the ramp begins, then backs off to the set current limit.

Panel fit and wiring

At 764 mm high x 478 mm wide x 241 mm deep, this is a full-frame soft starter — plan the gland plate and door swing accordingly. Clearance requirements: 100 mm above, 75 mm below, 10 mm in front, 5 mm at the sides, and 0 mm behind. Termination is via screw terminals — no special crimp tool needed for the power or control wiring.

Fieldbus and monitoring for retrofit

Onboard Modbus RTU, Modbus TCP, EtherNet/IP, and PROFIBUS mean this starter talks to nearly any existing PLC network — no need to gut the whole line's control architecture. The event list, error logbook, and trace function capture start profiles and fault sequences — useful for diagnosing intermittent trip issues on a conveyor or pump that's been running for years. Analog output configurable as 4-20 mA or 0-10 V lets you feed motor current or torque to an existing panel meter or DCS.

CE marked, UL approved, and CSA approved — the starter meets the declaration and certification requirements for European and North American installations. DC braking, motor heating, and auto-reset with remote reset capability are built in, reducing the need for external control relays.

MPN
3RW5553-6HA14