Rated 10 A at 30 °C ambient, the 5SL6110-6CC derates to 9.43 A at 40 °C and 8.51 A at 55 °C — a continuous load at 8 A in a warm enclosure is fine; a full 10 A draw in a 50 °C panel risks nuisance tripping. The 1 MW width (18 mm) snaps onto standard DIN rail; depth is 76 mm with a 70 mm installation depth behind the panel face, so it clears a 100 mm deep enclosure without gland-plate interference.

Siemens 5SL6110-6CC SENTRON MCB, 1P B-Curve 10A, 6kA
MPN 5SL6110-6CC
Active
Siemens SENTRON 5SL6110-6CC, 1-pole miniature circuit breaker, B-curve, 10 A rated current at 30 °C, 6 kA breaking capacity per IEC 60898, 1 MW width.
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026
Specifications
| Parameter | Value |
|---|---|
| Poles | 1 |
| IP rating | IP20 |
| Depth | 76 mm |
| Width | 18 mm |
| Height | 90 mm |
| Energy limitation class | 3 |
Product details
5SL6110-6CC Datasheet
MPN
5SL6110-6CC