Skip to main content
Siemens 5SL6110-6CC — 1-Pole MCB (DIN Rail)

Siemens 5SL6110-6CC SENTRON MCB, 1P B-Curve 10A, 6kA

MPN5SL6110-6CC
Active

Siemens SENTRON 5SL6110-6CC, 1-pole miniature circuit breaker, B-curve, 10 A rated current at 30 °C, 6 kA breaking capacity per IEC 60898, 1 MW width.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL6110-6CC — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Application suitabilityResidential buildings/infrastructure
5SL6110-6CC — Electrical & Protection
ParameterValue
Tripping characteristic classB
Rated value (EN 60898)6 kA
Energy limitation class3
Overvoltage categoryIII
5SL6110-6CC — Mounting & Connection
ParameterValue
Mounting positionany
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SL6110-6CC — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree2
Halogen-freeYes
Silicone-freeYes

Product details

Rated 10 A at 30 °C ambient, the 5SL6110-6CC derates to 9.43 A at 40 °C and 8.51 A at 55 °C — a continuous load at 8 A in a warm enclosure is fine; a full 10 A draw in a 50 °C panel risks nuisance tripping. The 1 MW width (18 mm) snaps onto standard DIN rail; depth is 76 mm with a 70 mm installation depth behind the panel face, so it clears a 100 mm deep enclosure without gland-plate interference.

MPN
5SL6110-6CC