Skip to main content
Siemens 5SM3352-6

Siemens 5SM3352-6 SENTRON RCCB, 25A 4P Type A, 10kA

MPN 5SM3352-6

Siemens SENTRON 5SM3 series RCCB, 4-pole, Type A, 25 A rated, 500 V AC, 10 kA short-circuit current rating, 50 Hz, DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SM3352-6 specifications
ParameterValue
Short circuit rating10 kA
Poles4
MountingDIN rail (REG)
Depth70 mm
Width36 mm
Height90 mm

Product details

The Siemens 5SM3352-6 is a 4-pole residual current circuit breaker (RCCB) from the SENTRON 5SM3 series, designed for 50 Hz systems. It carries a 25 A rated current at 500 V AC and a 10 kA short-circuit current rating, so it safely interrupts fault currents up to that level without cascading damage upstream in the distribution board. This is a Type A RCCB — it detects sinusoidal AC residual currents plus pulsating DC residual currents, which covers modern loads with half-wave rectification (switched-mode power supplies, variable-speed drives, LED drivers). The instantaneous design means no intentional time delay; it trips within the natural response time of the sensing coil.

Snaps onto a DIN rail (REG profile) and occupies 4 width units (36 mm wide, 90 mm tall, 70 mm deep). The supply can enter from top or bottom, which simplifies busbar routing in a crowded enclosure.

The 25 A rating holds at 40 °C and 45 °C. Above that, derate linearly: 24 A at 50 °C, 23 A at 55 °C, 22 A at 60 °C, 21 A at 65 °C, 20 A at 70 °C. Ambient operating range is -25 °C to 45 °C (maximum 75 °C, minimum -40 °C for storage).

MPN
5SM3352-6