Siemens 5SM3352-6 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SM3352-6 SENTRON RCCB, 25A 4P Type A, 10kA

MPN5SM3352-6

Siemens SENTRON 5SM3 series RCCB, 4-pole, Type A, 25 A rated, 500 V AC, 10 kA short-circuit current rating, 50 Hz, DIN rail mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Electrical Ratings

5SM3352-6 — Electrical Ratings
ParameterValue
Number of poles4
Overvoltage categoryIII

Identification

5SM3352-6 — Identification
ParameterValue
Product designationRCCB
Product design / constructionInstantaneous

Mechanical

5SM3352-6 — Mechanical
ParameterValue
Mounting positionany
Maximum45 °C
Minimum-25 °C
Width36 mm
Height90 mm
Depth70 mm
Installation depth70 mm

Environmental

5SM3352-6 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

What it is and what it does

The Siemens 5SM3352-6 is a 4-pole residual current circuit breaker (RCCB) from the SENTRON 5SM3 series, designed for 50 Hz systems. It carries a 25 A rated current at 500 V AC and a 10 kA short-circuit current rating, so it safely interrupts fault currents up to that level without cascading damage upstream in the distribution board. This is a Type A RCCB — it detects sinusoidal AC residual currents plus pulsating DC residual currents, which covers modern loads with half-wave rectification (switched-mode power supplies, variable-speed drives, LED drivers). The instantaneous design means no intentional time delay; it trips within the natural response time of the sensing coil.

Mounting and panel integration

Snaps onto a DIN rail (REG profile) and occupies 4 width units (36 mm wide, 90 mm tall, 70 mm deep). Mounting position is unrestricted — any orientation works. The supply can enter from top or bottom, which simplifies busbar routing in a crowded enclosure. IP20 with conductors connected; suitable for enclosed distribution boards only, not for wet or dusty environments.

Thermal derating and operating range

The 25 A rating holds at 40 °C and 45 °C. Above that, derate linearly: 24 A at 50 °C, 23 A at 55 °C, 22 A at 60 °C, 21 A at 65 °C, 20 A at 70 °C. Ambient operating range is -25 °C to 45 °C (maximum 75 °C, minimum -40 °C for storage). If the panel ambient runs hot — say, a sealed enclosure with drives — factor the derating into the load calculation.

Frequently asked questions

Where can I buy 5SM3352-6 and what is the lead time?

This part is sourced to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm lead-time commitment.

What is the difference between 5SM3352-6 and 5SY4310-7CV?

The 5SM3352-6 is a 4-pole Type A RCCB (residual current only) at 25 A, while the 5SY4310-7CV is a 4-pole MCB (overcurrent and short-circuit protection only) at 10 kA breaking capacity. They serve different protection functions — an RCCB detects earth leakage; an MCB detects overload and short-circuit. They are not drop-in substitutes; a complete distribution board typically uses both in series.

What compliance documentation does Siemens provide for 5SM3352-6?

The part carries designations per DIN EN 61346-2 and DIN EN 81346-2 (function letter F). It is silicon-free and finger-and-back-of-hand safe per the protection-against-electrical-shock feature. Specific RoHS/REACH/UL/IEC declarations are available from the manufacturer upon request.