Skip to main content
Siemens 5SM3746-5

Siemens SENTRON 5SM3746-5 RCCB, 4P, 63 A, Type B, 500 mA

MPN 5SM3746-5

Siemens SENTRON selective RCCB, 4-pole, 63 A, Type B, 500 mA, 10 kA, DIN rail.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SM3746-5 specifications
ParameterValue
Short circuit rating10 kA
Poles4
MountingDIN rail (REG)
Depth77 mm
Width72 mm
Height90 mm

Product details

The Siemens SENTRON 5SM3746-5 is a 4-pole selective residual current circuit breaker (RCCB) rated 63 A at 400 V AC, 50/60 Hz. The Type B residual-current detection means it trips on AC, pulsating DC, and smooth DC fault currents — the full spectrum you get from variable-speed drives, UPS systems, or photovoltaic inverters. The 500 mA rated tripping fault current is higher than a standard 30 mA RCD, so it's sized for selective coordination: it lets downstream 30 mA devices clear a ground fault first, only tripping this upstream unit if the fault persists or exceeds its threshold.

IP20 with conductors connected, so it's intended for enclosed panels only, not washdown or outdoor exposure.

Thermal derating — the real-world current

Above that, it steps down: 60.48 A at 50 °C, 57.96 A at 55 °C, 55.44 A at 60 °C, 52.92 A at 65 °C, and 50.4 A at 70 °C.

MPN
5SM3746-5