Skip to main content
Siemens 5SU1354-7VK32

Siemens 5SU1354-7VK32 SENTRON RCBO, 32 A, Type A, 10 kA

MPN 5SU1354-7VK32

Siemens SENTRON 5SU1 RCBO, 2-pole 1P+N, 32 A rated, Type A fault current, C tripping characteristic, 10 kA breaking capacity per EN 60898, IP20.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SU1354-7VK32 specifications
ParameterValue
Poles2
Temp operating max55 °C
Temp operating min-25 °C
Depth77 mm
Width36 mm
Height90 mm

Product details

SENTRON 5SU1354-7VK32 — RCBO for final circuits

Type A detection means it trips on sinusoidal AC residual currents plus pulsating DC fault currents up to 6 mA smooth DC — the right choice for circuits with single-phase rectifiers, switched-mode power supplies, or variable-speed drives that generate pulsating leakage.

Current derating and wiring capacity

Full rated current of 32 A holds at 30 °C ambient; derate progressively to 24.64 A at 70 °C. That thermal curve matters when the RCBO sits in a crowded enclosure — the 11.4 W maximum power dissipation adds to the internal temperature rise, so group several units and the derating compounds. Terminals accept solid or stranded conductors from 0.75 mm² up to 35 mm² — covers everything from 1.5 mm² lighting tails up to 10 mm² final-circuit feeders.

MPN