Skip to main content
Siemens 5SU1354-7VK32 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1354-7VK32 SENTRON RCBO, 32 A, Type A, 10 kA

MPN5SU1354-7VK32

Siemens SENTRON 5SU1 RCBO, 2-pole 1P+N, 32 A rated, Type A fault current, C tripping characteristic, 10 kA breaking capacity per EN 60898, IP20.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Electrical Ratings

5SU1354-7VK32 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII

Identification

5SU1354-7VK32 — Identification
ParameterValue
Product designationRCBO

Mechanical

5SU1354-7VK32 — Mechanical
ParameterValue
Mounting positionany
Maximum11.4 W
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm

Environmental

5SU1354-7VK32 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Electrical

5SU1354-7VK32 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

SENTRON 5SU1354-7VK32 — RCBO for final circuits

The Siemens SENTRON 5SU1354-7VK32 is a combined residual-current circuit breaker with overcurrent protection (RCBO) in a 2-module-wide (36 mm) package, rated 32 A at AC with a C tripping characteristic and Type A fault-current sensitivity. It breaks faults up to 10 kA per EN 60898 — a standard for household and similar installations — so it handles the typical prospective short-circuit current at the final sub-distribution board in a commercial or light-industrial panel. Type A detection means it trips on sinusoidal AC residual currents plus pulsating DC fault currents up to 6 mA smooth DC — the right choice for circuits with single-phase rectifiers, switched-mode power supplies, or variable-speed drives that generate pulsating leakage.

Current derating and wiring capacity

Full rated current of 32 A holds at 30 °C ambient; derate progressively to 24.64 A at 70 °C. That thermal curve matters when the RCBO sits in a crowded enclosure — the 11.4 W maximum power dissipation adds to the internal temperature rise, so group several units and the derating compounds. Terminals accept solid or stranded conductors from 0.75 mm² up to 35 mm² — covers everything from 1.5 mm² lighting tails up to 10 mm² final-circuit feeders. The 77 mm depth and 70 mm installation depth fit standard 85 mm deep distribution boards with clearance for outgoing cables.

Frequently asked questions

Where can I buy 5SU1354-7VK32 and how do I get a price?

This RCBO is sourced to order against an RFQ through independent distribution. Submit a request for quote; current pricing and availability are confirmed at quote time.

What is 5SU1354-7VK32's listed depth?

Depth is 77 mm, with an installation depth of 70 mm — fits standard 85 mm deep distribution boards.

What conductor sizes does 5SU1354-7VK32 accept?

Terminals accept solid or stranded conductors from 0.75 mm² up to 35 mm².

What compliance documentation does Siemens provide for 5SU1354-7VK32?

The RCBO is designed per EN 60898 (breaking capacity 10 kA), carries overvoltage category III, and is halogen-free and silicon-free. Standard Siemens declarations for RoHS and REACH are available on request.

MPN
5SU1354-7VK32