Skip to main content
Siemens 5SU1656-7KV16

Siemens 5SU1656-7KV16 FI/LS RCBO Type A, 16A C, 300mA, 6kA

MPN 5SU1656-7KV16

Siemens 5SU1656-7KV16 FI/LS-PROTECTOR, Type A (PSE/SSF), D=70mm, IΔn 300mA, 6kA, 1+N-pole, C 16A.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Product details

It's a Type A RCD with a 300 mA trip sensitivity, paired with a C-curve 16 A overcurrent characteristic and 6 kA breaking capacity.

Type A RCD means it detects pulsating DC fault currents — the kind you get from single-phase rectifiers, switched-mode power supplies, and variable-frequency drives. If your panel feeds electronics or motor drives downstream, a Type A is the minimum residual-current protection that won't nuisance-trip on smooth DC ripple. The 300 mA IΔn is a common specification for whole-circuit protection (not personnel shock protection, which typically uses 30 mA): it catches insulation faults and arcing without being so sensitive that cable capacitance trips it. The C-curve 16 A trips magnetically between 5× and 10× rated current (80–160 A), so it handles motor-starting inrush and transformer energization on loads up to roughly 3.5 kW single-phase.

MPN
5SU1656-7KV16