Siemens 5SV1316-7GV10 SENTRON RCBO, 10A, 30mA, Type A, 6kA

MPN 5SV1316-7GV10
Active

Siemens SENTRON RCBO, 2-pole (1P+N), 10 A rated, 30 mA residual current, Type A, C-curve, 6 kA / 10 kA breaking capacity, 18 mm wide, active production.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SV1316-7GV10 specifications
ParameterValue
Poles2
Depth77 mm
Width18 mm
Height90 mm
Energy limitation class3

Product details

The 10 A rated operational current and C-curve tripping characteristic mean it protects final circuits with moderate inrush, like lighting or small motor loads, while the 30 mA rated residual fault current provides additional protection against electric shock. The Type A designation means it detects both sinusoidal AC residual currents and pulsed DC residual currents — important for circuits with rectifiers or switching power supplies. The higher IEC figure applies when the RCBO is used in industrial distribution where the prospective short-circuit current may exceed the domestic standard. The 1P+N configuration switches the line conductor and disconnects the neutral, which is standard for single-phase final circuits in TN or TT systems.

Halogen-free and silicon-free construction. The neutral conductor is switched, and touch protection is provided.