Skip to main content
Siemens 5SV1613-1KK06

Siemens 5SV1613-1KK06 SENTRON RCBO, 6 A, C-curve, 300 mA, 1P

MPN 5SV1613-1KK06
Active

Siemens SENTRON RCBO, 5SV1613-1KK06, 1P+N, 6 A rated, C characteristic, 300 mA residual current, 4.5 kA breaking capacity, 18 mm width, 77 mm depth.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SV1613-1KK06 specifications
ParameterValue
Poles2
Depth77 mm
Width18 mm
Height90 mm
Energy limitation class3

Product details

The C-curve means it holds through motor inrush and capacitive loads that would nuisance-trip a B-curve, but trips fast on a hard short — standard choice for general-purpose socket outlets and small equipment feeds.

At 40 °C it derates to 5.64 A, at 50 °C to 5.28 A, and at 70 °C to 4.44 A — so if this lives in a hot panel near a drive or transformer, size the load accordingly. The 300 mA residual current is an AC-type trip (sine-wave faults only), not A-type (pulsating DC) or F-type (mixed-frequency). That matters: if the downstream load includes a VFD, LED driver, or single-phase rectifier that can produce smooth DC fault current, an AC-type RCBO may not trip within the required time. Verify the load's fault signature before committing this to the BOM. The 1P+N design switches the line conductor only; the neutral is switched but not protected against overcurrent. Two physical poles, one with overcurrent protection. That is standard for single-phase final circuits where the neutral is not fused. The 18 mm width (1 modular unit) saves DIN rail space — you can pack 12 of these per 12-module enclosure row.

Mounts in any position on DIN rail. Depth is 77 mm (70 mm installation depth), so it fits standard distribution boards with 80 mm+ internal depth. Halogen-free and silicon-free construction, which matters for panels in high-fire-risk zones (tunnels, data centers) where corrosive gas from a fault must be minimized.

MPN
5SV1613-1KK06