Skip to main content
Siemens 5SV9316-6PK06

Siemens 5SV9316-6PK06 SENTRON RCD Circuit Breaker, Type A, 3

MPN 5SV9316-6PK06
Active

Siemens SENTRON 5SV9 series, RCD-operated circuit breaker, Type A, 30 mA, 6 kA, B curve, 6 A at 30 °C, 2-pole 1P+N, 77 mm depth, 18 mm width, 90 mm height.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SV9316-6PK06 specifications
ParameterValue
Poles2
Depth77 mm
Width18 mm
Height90 mm

Product details

It trips on both overcurrent (B curve, 6 A at 30 °C) and earth leakage (Type A, 30 mA), so it protects a single-phase final subcircuit against overload, short-circuit, and indirect contact in one DIN-rail unit. The Type A fault-current detection handles pulsating DC residual currents (e.g. from rectifiers, switched-mode supplies, or washing-machine drives) that a plain Type AC RCD would miss.

The 18 mm width (1 width unit) means it occupies a single slot — useful when panel fill factor is tight. Depth is 77 mm (70 mm installation depth), so it clears most shallow enclosures. IP20 with the distribution board installed and conductors connected — standard for enclosed panel gear. Supply connects from below (line at bottom, load at top per the evidence).

At 40 °C it derates to 5.64 A; at 45 °C to 5.46 A; at 50 °C to 5.22 A; at 55 °C to 5.04 A.

MPN