Skip to main content
Siemens 5SY4216-6KK11

Siemens 5SY4216-6KK11 SENTRON MCB, 2P B-16 A, 10/20 kA

MPN 5SY4216-6KK11

Siemens SENTRON 5SY4216-6KK11, 2-pole miniature circuit breaker, B-curve, 16 A rated, 10 kA (EN 60898) / 20 kA (IEC 60947-2), 2 MW, IP20, halogen-free, silicon-free, rail-mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SY4216-6KK11 specifications
ParameterValue
Poles2
IP ratingIP20
MountingQuick assembly system
Temp operating max75 °C
Temp operating min55 °C
Depth76 mm
Width36 mm
Height90 mm
Energy limitation class3

Product details

Deployment context — where this part goes

The design is flagged for railway applications, which typically demands wider temperature range and vibration resistance — the -40 °C to 75 °C operating range confirms that.

Thermal derating — the real-world current limit

The 16 A rating holds at 35 °C. Above that, derate linearly: 15.23 A at 40 °C, 14.83 A at 45 °C, 14.43 A at 50 °C, 14 A at 55 °C, 13.57 A at 60 °C. If the panel ambient runs at 50 °C, the breaker's continuous current limit is 14.43 A — not 16 A. That's the number to put in the BOM load calculation.

Sourcing and lifecycle — current production, quoted to order

MPN
5SY4216-6KK11