Skip to main content
Siemens 5SY4216-6KK11 — 2-Pole MCB (DIN Rail)

Siemens 5SY4216-6KK11 SENTRON MCB, 2P B-16 A, 10/20 kA

MPN5SY4216-6KK11

Siemens SENTRON 5SY4216-6KK11, 2-pole miniature circuit breaker, B-curve, 16 A rated, 10 kA (EN 60898) / 20 kA (IEC 60947-2), 2 MW, IP20, halogen-free, silicon-free, rail-mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY4216-6KK11 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentMechanical engineering / industry
5SY4216-6KK11 — Electrical
ParameterValue
Number of poles2
5SY4216-6KK11 — Protection
ParameterValue
Tripping characteristic classB
Overvoltage categoryIII
5SY4216-6KK11 — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SY4216-6KK11 — Environmental
ParameterValue
Pollution degree3
5SY4216-6KK11 — Specifications
ParameterValue
Energy Limitation Class3

Product details

Deployment context — where this part goes

The design is flagged for railway applications, which typically demands wider temperature range and vibration resistance — the -40 °C to 75 °C operating range confirms that.

Thermal derating — the real-world current limit

The 16 A rating holds at 35 °C. Above that, derate linearly: 15.23 A at 40 °C, 14.83 A at 45 °C, 14.43 A at 50 °C, 14 A at 55 °C, 13.57 A at 60 °C. If the panel ambient runs at 50 °C, the breaker's continuous current limit is 14.43 A — not 16 A. That's the number to put in the BOM load calculation.

Sourcing and lifecycle — current production, quoted to order

Frequently asked questions

What is the width of 5SY4216-6KK11?

36 mm, which is 2 modular width units on a standard DIN rail.

MPN
5SY4216-6KK11