Skip to main content
Siemens 5SY4602-5

Siemens 5SY4602-5 SENTRON MCB, 4P, 2 A, Char A, 10/35 kA

MPN 5SY4602-5
Active

Siemens SENTRON 5SY4602-5, 4-pole miniature circuit breaker, 2 A rated current, tripping characteristic A, 10 kA (EN 60898) / 35 kA (IEC 60947-2), 50/60 Hz, IP20, 4 MW.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SY4602-5 specifications
ParameterValue
Poles4
IP ratingIP20
MountingQuick assembly system
Temp operating max75 °C
Temp operating min55 °C
Depth76 mm
Width72 mm
Height90 mm

Product details

It is designed for branch-circuit protection in industrial control panels, suited for mechanical engineering and industry environments. Characteristic A trips between 2 and 3 times rated current, making it appropriate for protecting semiconductor loads or long cable runs where standard B or C curves might not coordinate.

Temperature derating and real-world current

The 2 A rating is at 35 °C ambient. At 40 °C the breaker carries 1.9 A, at 45 °C it is 1.85 A, at 50 °C it drops to 1.8 A, at 55 °C to 1.75 A, and at 60 °C to 1.7 A. If the panel runs warm — common in a densely packed enclosure — factor these numbers into the load calculation rather than relying on the 35 °C figure.

MPN
5SY4602-5