Skip to main content
Siemens 5SY8232-8BB08

Siemens 5SY8232-8BB08 SENTRON MCB, D Curve, 2-Pole, 30 kA IE

MPN 5SY8232-8BB08
Active

Siemens SENTRON 5SY8232-8BB08, 2-pole miniature circuit breaker, D tripping characteristic, 30 kA breaking capacity at 400 V AC per IEC 60947-2, width 36 mm, depth 76 mm.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SY8232-8BB08 specifications
ParameterValue
Poles2
IP ratingIP20
MountingQuick assembly system
Temp operating max75 °C
Temp operating min55 °C
Depth76 mm
Width36 mm
Height90 mm

Product details

Two poles, no neutral switching, so it lands on a 2-module DIN-rail footprint (36 mm wide, 76 mm deep) and mounts in any orientation. Under UL 1077 it's rated 5 kA, so if the panel ships to a North American site and the spec calls for UL 489 branch-circuit protection, verify the application; this is a supplementary protector per UL 1077.

D curve — what it means for the line

That's the right window for loads that draw a short-duration surge — think a 15 kW motor direct-on-line or a bank of control transformers. The breaker ignores the inrush and only clears on a genuine bolted fault. No thermal element in the trip mechanism (the design is 'only magnetic tripping operation'), so ambient temperature doesn't shift the trip threshold the way it would on a thermal-magnetic. That's useful in a warm cabinet or a panel near a furnace line. The surrounding temperature influence is spelled out: max 95% RH at 55 °C, derating to 55% at 70 °C and 35% at 75 °C.

Mechanical and environmental

Vibration resistance per IEC 60068-2-6: ±1 mm displacement at 5–25 Hz, then 50 m/s² acceleration at 25–150 Hz. That's a standard industrial vibration profile — the breaker holds its contacts and trip calibration under pump or conveyor vibration. IP20 with connected conductors — finger-safe terminals once wired, but the busbar area is open. Sealable (yes), halogen-free, silicon-free. The quick-assembly fastening system is the standard SENTRON DIN-rail clip; no tools needed for mounting or removal.

The breaker accepts add-on auxiliary switches, shunt trips, and alarm contacts via the product extension interface. That means the same physical unit can be specified for a panel that later needs remote trip indication or undervoltage release — the auxiliaries clip on the right side without replacing the breaker.