Skip to main content
Siemens 6EP1967-2AA00

Siemens 6EP1967-2AA00 DIN rail power supply, 10 A

MPN 6EP1967-2AA00
Active

Siemens 6EP1967-2AA00 DIN rail mounted power supply, 100-480 V AC input, 0-10 A single output, UL 508 / cULus listed, snaps onto EN 60715 rail.

$50.80 – $60.00 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

6EP1967-2AA00 specifications
ParameterValue
Frequency47 ... 63 Hz
Phases1-phase
IP ratingIP20
MountingSnaps onto DIN rail EN 60715 35x7.5/15
Depth91 mm
Width22.5 mm
Height80 mm
I/O channels1

Product details

Panel placement and DIN-rail footprint

The Siemens 6EP1967-2AA00 snaps onto EN 60715 35x7.5/15 DIN rail, with 91 mm enclosure depth and a 50 mm top clearance — the side clearances are listed at 0 mm, so adjacent devices can be butted against it on the rail without forcing extra horizontal pitch.

AC input envelope and feeder protection

The input side takes L and N on a single screw terminal each, accepting 0.5-2.5 mm² conductors, and the upstream feeder is protected by a circuit breaker max. 10 A.

Output rating and how to wire it

Single output rated 0-10 A, wired to L and N on the same 0.5-2.5 mm² screw-terminal pitch as the input — the symmetrical terminal block keeps the panel layout uniform, and the 10 A ceiling is the figure the downstream fuse or MCB must coordinate against. Internal protection is a non-reversible thermal fuse on overload, so an output short latches the unit off rather than cycling.

Thermal envelope and hold-up

Mains hold-up is typically 120 ms, which bridges short utility dips without the load dropping out.

Approvals and where it is accepted

CE-marked, cULus-listed to UL 508 and CSA C22.2 No. 107.1 (File E197259), and carries EAC approval; the safety standard cited is EN 60950-1 and the enclosure is IP20, so it sits inside a closed panel rather than open to the shop floor. ATEX, IECEx, FM, DNV GL and UL hazardous-location listings are all marked No on this variant — for hazardous-area or marine-class service, a different line must be specified.

MPN
6EP1967-2AA00