Panel placement and DIN-rail footprint
The Siemens 6EP1967-2AA00 snaps onto EN 60715 35x7.5/15 DIN rail, with 91 mm enclosure depth and a 50 mm top clearance — the side clearances are listed at 0 mm, so adjacent devices can be butted against it on the rail without forcing extra horizontal pitch.
AC input envelope and feeder protection
The input side takes L and N on a single screw terminal each, accepting 0.5-2.5 mm² conductors, and the upstream feeder is protected by a circuit breaker max. 10 A.
Output rating and how to wire it
Single output rated 0-10 A, wired to L and N on the same 0.5-2.5 mm² screw-terminal pitch as the input — the symmetrical terminal block keeps the panel layout uniform, and the 10 A ceiling is the figure the downstream fuse or MCB must coordinate against. Internal protection is a non-reversible thermal fuse on overload, so an output short latches the unit off rather than cycling.
Thermal envelope and hold-up
Mains hold-up is typically 120 ms, which bridges short utility dips without the load dropping out.
Approvals and where it is accepted
CE-marked, cULus-listed to UL 508 and CSA C22.2 No. 107.1 (File E197259), and carries EAC approval; the safety standard cited is EN 60950-1 and the enclosure is IP20, so it sits inside a closed panel rather than open to the shop floor. ATEX, IECEx, FM, DNV GL and UL hazardous-location listings are all marked No on this variant — for hazardous-area or marine-class service, a different line must be specified.