Skip to main content
ABB 1SDA068113R1

ABB 1SDA068113R1 XT4N 160 MA Motor Protection Circuit Breake

MPN 1SDA068113R1

ABB XT4N 160 MA motor protection circuit breaker, 1SDA068113R1, 3-pole, rated In 12.5 A, Iu 160 A, 690 V, 50/60 Hz, with MA trip unit.

$433.00 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

1SDA068113R1 specifications
ParameterValue
Product typeXT4N 160 MA 12,5 Im=62,5...125 3p F F
Voltage690 V
Current12.5 A
Frequency50/60 Hz
Poles3 poles
Weight2.1 Kg
DimensionsXT4

Product details

The ABB 1SDA068113R1 is a 3-pole motor protection circuit breaker from the XT4N 160 MA series, sized for motor branch circuits. It carries a rated current In of 12.5 A and a frame current Iu of 160 A, with an MA trip unit — magnetic-only, no thermal element, so it relies on an external overload relay for thermal protection. Rated voltage is 690 V at 50/60 Hz.

The MA trip unit is adjustable (Im=62.5...125 A on the type label), so you set the magnetic trip threshold to match the motor's starting inrush — typically 8–12× FLA for a standard induction motor. No thermal overload means you pair this with a separate overload relay (e.g., ABB Tmax or electronic relay) for the motor's thermal protection.

MPN
1SDA068113R1