The TMA trip unit's thermal dial adjusts the overload pickup (Ir) between 0.4× and 1× of the rated frame current; the magnetic short-circuit pickup (Im) adjusts between 5× and 10× Ir. Wire the line and load side per the nameplate torque values; the FF UL variant carries UL 489 listing for branch circuit protection in North American panels. Spring-cage or screw terminals accept copper conductors sized for the 400 A continuous rating — verify lug ampacity and temperature rise for the specific cable size.

ABB XT5SU330ABFN000XXX XT5S 400A MCCB, TMA 300-3000A 3P
MPN XT5SU330ABFN000XXX
ABB XT5S series, XT5S 400 frame molded case circuit breaker, TMA 300-3000 A thermal-magnetic adjustable trip unit, 3-pole, FF UL version, order code XT5SU330ABFN000XXX.