Skip to main content
Siemens 3RT2027-1AG60

Siemens 3RT2027-1AG60 SIRIUS Power Contactor, Size S0, 45 mm

MPN 3RT2027-1AG60
Active

Siemens SIRIUS power contactor, Size S0, 45 mm width, screw and snap-on mounting onto 35 mm DIN rail per DIN EN 60715, auxiliary switch included, current lifecycle stage.

$55.88 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RT2027-1AG60 specifications
ParameterValue
Depth97 mm
Width45 mm
Height85 mm
Arcing time10 ... 10 ms

Product details

Duty-cycle and switching frequency

This contactor is rated for AC-3 switching (squirrel-cage motor starting) at 750 operating cycles per hour maximum, and AC-4 (plugging/inching) at 250 cycles per hour. The AC-1 resistive load rate is 1,000 cycles per hour. Those numbers tell you the thermal limit of the contactor under different load types — AC-4 generates more arc energy per cycle, so the allowable rate drops. For a conveyor line running continuous start/stop, the AC-3 rate is the one that governs.

The built-in auxiliary switch is rated for 10 A at 24 V, 2 A at 48/60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, and 3 A at 400 V. At 230 V it carries a 5 hp motor load. These are the switching capacities for the control circuit — match them to your PLC output or relay coil draw. The 10 A at 24 V is generous for most DC control circuits.

Mechanical endurance and temperature range

The storage limit covers handling and shelf life, not running conditions.

Wiring and dimensions

Main contact terminals accept solid or stranded wire from 1 to 10 mm², or two conductors per terminal (2x 0.5–1.5 mm² or 2x 0.75–2.5 mm²). The contactor body is 85 mm high, 97 mm deep, and 45 mm wide. That 97 mm depth is the dimension from the DIN rail face to the farthest projection — check your enclosure depth before panel layout.

MPN