Siemens 3RV1011-1CA10-ZW97

Siemens 3RV1011-1CA10-ZW97 SIRIUS Motor Protection Circuit B

MPN 3RV1011-1CA10-ZW97
Active

Siemens SIRIUS, motor protection circuit breaker, 3RV1011-1CA10-ZW97, Trip Class 10, 100 kA interrupting capacity at 400 V, phase failure detection, screw and snap-on mounting onto 35 mm DIN rail.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RV1011-1CA10-ZW97 specifications
ParameterValue
Depth75 mm
Width45 mm
Height90 mm
Trip classCLASS 10

Product details

Motor protection circuit breaker — SIRIUS 3RV1011-1CA10-ZW97

Rated interrupting capacity reaches 100 kA at 240 V, 400 V, and 500 V, dropping to 2 kA at 690 V.

At 400 V, the datasheet specifies a gL/gG 35 A backup fuse; at 500 V and 690 V, gL/gG 25 A. At 240 V, no backup fuse is required. These are the coordination limits — exceed them and the interrupting capacity of the device alone is what clears the fault. The 2 kA rating at 690 V is a hard ceiling; if the available fault current at 690 V exceeds that, a current-limiting upstream device is mandatory.

The lifecycle stage for this order code is listed as current, meaning the manufacturer continues to produce it as a standard catalog item. No successor has been announced.

Mounting clearances and wiring

Clearance requirements per the datasheet: 20 mm upwards, 20 mm downwards, 9 mm at the side, 0 mm forwards, 0 mm backwards. These are the minimum free air spaces needed for heat dissipation and arc venting — not optional for maintaining the SCCR rating. Main circuit terminals accept 2×(0.5…1.5 mm²) or 2×(0.75…2.5 mm²) solid or stranded, with M3 screw-type terminals.

Environmental limits

The rated voltage range is 20…690 V. Maximum switching frequency under AC-3 or AC-3e duty is 15 operations per hour.