Skip to main content
Siemens 3RW5217-3AC14

Siemens 3RW5217-3AC14 Soft Starter, 15.5 A, 200-480 V

MPN 3RW5217-3AC14
Active

Siemens 3RW5217-3AC14 soft starter, 15.5 A minimum, 200-480 V, Trip Class 10A/10E/20E, PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, PROFINET, UL, CSA, CE.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RW5217-3AC14 specifications
ParameterValue
Mountingscrew fixing
Depth152 mm
Width170 mm
Height275 mm
Trip classCLASS 10 A (default) / 10E / 20E; acc. to IEC 60947-4-2
Service factor1
Digital output version2 normally-open contacts (NO) / 1 changeover contact (CO)

Product details

Trip class and motor protection profile

The 3RW5217-3AC14 is set to Trip Class 10A by default, with selectable 10E and 20E curves per IEC 60947-4-2. Minimum load is 15 % of the smallest settable Ie, so the unit handles lightly loaded motors without dropping out of the start ramp.

Fieldbus and control network integration

This soft starter carries onboard PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET interfaces — no separate communication module needed for most architectures. PROFINET standard with PROFIenergy support is included for energy monitoring during idle phases. The analog output is configurable as 4-20 mA or 0-10 V (via the High Feature HMI), and the unit logs errors to an internal logbook when the optional accessory is fitted.

Mounting and panel clearance

Dimensions are 275 mm high, 170 mm wide, and 152 mm deep — screw-fixed to a vertical surface. Clearance requirements: 100 mm above, 75 mm below, 10 mm in front, 5 mm at the sides, and 0 mm behind. Mounting position allows ±90° rotation and ±22.5° tilt front-to-back on a vertical surface, giving flexibility in tight enclosures.

Operating temperature and derating

Rated for -25 to +60 °C during operation, but derating applies above 40 °C — factor in the thermal load if the panel ambient runs hot. Shock resistance is 15 g for 11 ms; potential contact lifting starts at 12 g for 11 ms, so the unit is robust for machine-mounted installations.

Approvals and compliance

Carries UL, CSA, and CE markings — accepted for North American and European installations without additional certification steps.

MPN