Skip to main content
Siemens 3RW5217-3TC05

Siemens 3RW5217-3TC05 Soft Starter, SIRIUS, 15.5 A

MPN 3RW5217-3TC05
Active

Siemens SIRIUS 3RW5217-3TC05 soft starter, 15.5 A minimum, 200-600 V rated, Class 10A, screw fixing, 275 x 170 x 152 mm.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RW5217-3TC05 specifications
ParameterValue
Mountingscrew fixing
Depth152 mm
Width170 mm
Height275 mm
Trip classCLASS 10 A (default) / 10E / 20E; acc. to IEC 60947-4-2
Service factor1

Product details

Rated voltage and current — what they mean for the motor

The 3RW5217-3TC05: The rated voltage range is 200 to 600 V, covering common low-voltage networks from 208 V to 480 V and 600 V. The minimum settable current is 15.5 A, which sets the lower bound for the motor FLA the starter can protect — below that, the overload curve cannot be calibrated.

Trip class and starting duty

Trip class is selectable: CLASS 10A (default), 10E, or 20E, per IEC 60947-4-2. Class 20E allows a longer start, useful for high-inertia loads like conveyors or crushers.

Fieldbus connectivity — PROFIBUS, Modbus, PROFINET

The starter supports PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET natively — no separate communication module required for these protocols. This makes it a drop-in for most Siemens and third‑party PLC architectures without adding a gateway.

Pump-specific features — ramp down and soft torque

Pump Ramp Down and Soft Torque are built in. Pump Ramp Down extends the deceleration time to reduce water hammer in pump systems. Soft Torque reduces starting torque below the motor's locked-rotor torque, which is useful for conveyors or other loads that must accelerate gently.

Mounting and clearances

Minimum clearances: 100 mm upwards, 75 mm downwards, 10 mm forwards, 5 mm sideways, and 0 mm backwards — the back can sit flush against the panel backplate.

Approvals and compliance

Carries CE marking, UL approval, and CSA approval — accepted across North American and European installations without additional certification work.

MPN
3RW5217-3TC05