Skip to main content
Siemens 3RW5513-1HA04

Siemens 3RW5513-1HA04 Soft Starter, 200-480V, ATEX

MPN 3RW5513-1HA04
Active

Siemens 3RW5513-1HA04 soft starter, 200-480 V rated voltage, ATEX and IECEx certified, trip class 10A/10E/20E/30E, PROFIBUS/Modbus/EtherNet/IP, 152 x 170 x 275 mm.

$689.61 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RW5513-1HA04 specifications
ParameterValue
Mountingscrew fixing
Depth152 mm
Width170 mm
Height275 mm
Trip classCLASS 10 A / 10E (default) / 20E / 30E; acc. to IEC 60947-4-2
Service factor1.15

Product details

What the 3RW5513-1HA04 brings to a motor start

This soft starter covers the 200-480 V range, so it fits standard North American 480 V and European 400 V distribution without a transformer tap. Trip class is selectable from CLASS 10A through 30E per IEC 60947-4-2 — you can set it for a quick start on a light load or stretch the ramp for a high-inertia conveyor without tripping. It carries ATEX and IECEx certification, meaning it can sit in a Zone 2 or Zone 22 area if the rest of the panel is rated for it. Fieldbus options include PROFIBUS, Modbus RTU, Modbus TCP, and EtherNet/IP — one part number covers the common industrial networks without a separate comms module.

Mounting and panel fit

The unit measures 152 mm deep by 170 mm wide by 275 mm tall — it needs 100 mm clearance above, 10 mm in front, 75 mm below, and 5 mm at the sides for airflow and wiring access. Terminals accept solid wire: two conductors at 1.0-2.5 mm² and two at 2.5-10 mm² per pole, using screw terminals.

Control features that matter on the line

Voltage ramp and pump ramp down are built in — the pump ramp down reduces water hammer on stop, which saves mechanical wear on check valves and piping. Torque control mode lets the starter regulate motor torque during acceleration, useful for soft-starting a loaded conveyor without shock. A breakaway pulse delivers a short torque burst to break loose a seized or high-friction load before the ramp begins. DC braking and combined braking are available for fast stops without a mechanical brake. The analog output can be configured as 4-20 mA or 0-10 V to feed motor current or torque to a PLC or panel meter. Service factor is 1.15, meaning the starter can handle a 15% continuous overload above the motor FLA rating without nuisance tripping.

Diagnostics and commissioning aids

An event list, error logbook, and trace function are all on board — you can review the last several start/stop events and fault conditions without a laptop. Accuracy class 5 per IEC 61557-12 means the current measurement is within 5% — adequate for protection and monitoring, not for billing-grade metering. Firmware updates are field-loadable, so you can apply Siemens patches without swapping hardware. Four parameterizable settings let you store different start profiles and switch between them for different motor loads on the same starter.