Skip to main content
Siemens 3RW5513-1HA04 — Soft Starters

Siemens 3RW5513-1HA04 Soft Starter, 200-480V, ATEX

MPN3RW5513-1HA04
Active

Siemens 3RW5513-1HA04 soft starter, 200-480 V rated voltage, ATEX and IECEx certified, trip class 10A/10E/20E/30E, PROFIBUS/Modbus/EtherNet/IP, 152 x 170 x 275 mm.

$689.61Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RW5513-1HA04 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS
3RW5513-1HA04 — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)5.5 kW
Rated motor power at 230 V (40 °C)3 kW
Rated operational current at 40 °C22.5 A
Rated operational current at 50 °C19.9 A
Rated operational current at 60 °C18.2 A
Rated insulation voltage480 V
Minimum settable current (% of Ie)10 %; Relative to set Ie
Power loss during startup (50 °C)166 W
3RW5513-1HA04 — Control & Connection
ParameterValue
Control supply voltage typeAC/DC
Rated voltage at 50 Hz24 V
Rated voltage at 60 Hz24 V
Main circuit terminal typescrew-type terminals
Control circuit wire range, solid1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
Control circuit wire range, finely stranded (with ferrule)1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
Analog outputYes; 4 ... 20 mA (default) / 0 ... 10 V
Auxiliary contact rated current, AC-15 at 250 V3 A
Auxiliary contact rating (UL)R300-B300
Control supply voltage tolerance, AC 50 Hz (max.)20 %
Control supply voltage tolerance, AC 50 Hz (min.)-20 %
Control supply voltage tolerance, AC 60 Hz (max.)20 %
Control supply voltage tolerance, AC 60 Hz (min.)-20 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
Operating voltage tolerance, inside-delta (max.)10 %
Operating voltage tolerance, inside-delta (min.)-15 %
3RW5513-1HA04 — Protection & Features
ParameterValue
Motor overload protectionYes; Full motor protection (thermistor motor protection and electronic motor overload protection) / When using the motor overload protection according to ATEX, an upstream contactor is required in inside-delta circuit.
Thermistor motor protectionYes; Type A PTC or Klixon / Thermoclick
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2
3RW5513-1HA04 — Mechanical
ParameterValue
Height275 mm
Width170 mm
Depth152 mm
Weight2.3 kg
Mounting positionVertical (can be rotated +/- 90° and tilted forward or backward +/- 22.5°)
Fastening methodscrew fixing
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm
3RW5513-1HA04 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude5 000 m; Derating as of 1000 m, see catalog
Ambient class during operation (IEC 60721)3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)
3RW5513-1HA04 — Specifications
ParameterValue
Trip ClassCLASS 10A / 10E (default) / 20E / 30E; acc. to IEC 60947-4-2
Number Of Controlled Phases3
Utilization category according to IEC 60947-4-2AC 53a
Product Feature Integrated Bypass Contact SystemYes
Start-Up Ramp Time Of Soft Starter0 ... 360 s
Ramp-Down Time Of Soft Starter0 ... 360 s
3RW5513-1HA04 — Electrical
ParameterValue
Current Limiting Value [%] Adjustable125 ... 800 %
Starting Voltage [%]20 ... 100 %
Stopping Voltage [%]50 %; non-adjustable

Product details

What the 3RW5513-1HA04 brings to a motor start

This soft starter covers the 200-480 V range, so it fits standard North American 480 V and European 400 V distribution without a transformer tap. Trip class is selectable from CLASS 10A through 30E per IEC 60947-4-2 — you can set it for a quick start on a light load or stretch the ramp for a high-inertia conveyor without tripping. It carries ATEX and IECEx certification, meaning it can sit in a Zone 2 or Zone 22 area if the rest of the panel is rated for it. Fieldbus options include PROFIBUS, Modbus RTU, Modbus TCP, and EtherNet/IP — one part number covers the common industrial networks without a separate comms module.

Mounting and panel fit

The unit measures 152 mm deep by 170 mm wide by 275 mm tall — it needs 100 mm clearance above, 10 mm in front, 75 mm below, and 5 mm at the sides for airflow and wiring access. Terminals accept solid wire: two conductors at 1.0-2.5 mm² and two at 2.5-10 mm² per pole, using screw terminals.

Control features that matter on the line

Voltage ramp and pump ramp down are built in — the pump ramp down reduces water hammer on stop, which saves mechanical wear on check valves and piping. Torque control mode lets the starter regulate motor torque during acceleration, useful for soft-starting a loaded conveyor without shock. A breakaway pulse delivers a short torque burst to break loose a seized or high-friction load before the ramp begins. DC braking and combined braking are available for fast stops without a mechanical brake. The analog output can be configured as 4-20 mA or 0-10 V to feed motor current or torque to a PLC or panel meter. Service factor is 1.15, meaning the starter can handle a 15% continuous overload above the motor FLA rating without nuisance tripping.

Diagnostics and commissioning aids

An event list, error logbook, and trace function are all on board — you can review the last several start/stop events and fault conditions without a laptop. Accuracy class 5 per IEC 61557-12 means the current measurement is within 5% — adequate for protection and monitoring, not for billing-grade metering. Firmware updates are field-loadable, so you can apply Siemens patches without swapping hardware. Four parameterizable settings let you store different start profiles and switch between them for different motor loads on the same starter.

Approvals and compliance documentation

ATEX and IECEx certification means the documentation package includes the EU-type examination certificate and the IECEx certificate of conformity for hazardous-area approval.

Frequently asked questions

What trip classes does the 3RW5513-1HA04 support?

It supports CLASS 10A, 10E, 20E, and 30E per IEC 60947-4-2. The default is 10A or 10E, and you can select a higher class for high-inertia loads.

Can the 3RW5513-1HA04 be used in a hazardous area?

Yes, it carries ATEX and IECEx certification, so it is suitable for use in Zone 2 or Zone 22 hazardous locations when installed per the certification conditions.

What fieldbus protocols does the 3RW5513-1HA04 support?

It supports PROFIBUS, Modbus RTU, Modbus TCP, and EtherNet/IP — all integrated without a separate communication module.

What compliance documentation does Siemens provide for the 3RW5513-1HA04?

The starter carries UL, CSA, and CE marking, plus ATEX and IECEx certificates for hazardous-area use. These cover the standard regulatory requirements for North America and Europe.

MPN
3RW5513-1HA04