Skip to main content
Siemens 3VA1025-3ED36-0AA0

Siemens 3VA1025-3ED36-0AA0 SENTRON MCCB, 25 A, 3-Pole, 75.6

MPN 3VA1025-3ED36-0AA0
Active

Siemens SENTRON 3VA1025-3ED36-0AA0, 3-pole molded case circuit breaker, 25 A rated current, TM210 thermal-magnetic release, breaking capacity 75.6 kA at 240 V.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3VA1025-3ED36-0AA0 specifications
ParameterValue
Insulation voltage ui800 V
Poles3
Depth70 mm
Width76.2 mm
Height130 mm

Product details

Line protection MCCB with thermal derating clarity

It carries a full rated current of 25 A from 40 °C up to 50 °C ambient — no derating needed in a typical 40 °C panel — then steps down to 24 A at 55 °C and 23 A at 70 °C, which is the maximum operating temperature. That thermal curve lets you size the breaker for a 25 A load without oversizing for a warm enclosure, as long as ambient stays under 50 °C.

Breaking capacity drops with system voltage: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at both 500 V and 690 V. At 240 V it handles high-fault commercial services; at 415 V it covers most European industrial distribution panels.

Panel fit and environmental ratings

Dimensions are 130 mm high, 76.2 mm wide, 70 mm deep — a standard 3-pole MCCB footprint that fits SENTRON distribution blocks and panel-mounting feet. Maximum power loss is 8.5 W, which matters for thermal coordination inside a sealed enclosure.

MPN
3VA1025-3ED36-0AA0