Skip to main content
Siemens 5SL3006-7KL

Siemens 5SL3006-7KL SENTRON MCB, 6A C-curve 1P+N, 4.5kA

MPN 5SL3006-7KL
Active

Siemens SENTRON 5SL3006-7KL, miniature circuit breaker compact, 1P+N, 6 A rated current AC, C tripping characteristic, 4.5 kA breaking capacity per IEC/EN 60898-1, 1 modular width unit.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SL3006-7KL specifications
ParameterValue
IP ratingIP20
Mountingstandard rail
Temp operating max45 °C
Temp operating min-25 °C
Depth76 mm
Width18 mm
Height90 mm
Energy limitation class3

Product details

Commissioning note — 5SL3006-7KL

Rated 6 A at 30 °C with a C tripping characteristic, it breaks faults up to 4.5 kA per IEC/EN 60898-1. That C-curve means it holds through motor inrush (5–10× rated) and trips on sustained overloads, making it a standard fit for general-purpose branch circuits in residential and light-commercial panels.

Panel fit and derating

Rated current derates with ambient temperature: 5.76 A at 40 °C, 5.51 A at 50 °C, 5.25 A at 60 °C.

Current-production status. The 5SL3006-7KL carries approvals to IEC/EN 60898-1 and GB/T 10963.1. Halogen-free and silicon-free construction.

MPN
5SL3006-7KL