Commissioning note — 5SL3006-7KL
Rated 6 A at 30 °C with a C tripping characteristic, it breaks faults up to 4.5 kA per IEC/EN 60898-1. That C-curve means it holds through motor inrush (5–10× rated) and trips on sustained overloads, making it a standard fit for general-purpose branch circuits in residential and light-commercial panels.
Panel fit and derating
Rated current derates with ambient temperature: 5.76 A at 40 °C, 5.51 A at 50 °C, 5.25 A at 60 °C.
Current-production status. The 5SL3006-7KL carries approvals to IEC/EN 60898-1 and GB/T 10963.1. Halogen-free and silicon-free construction.