Siemens SENTRON 5SU1324-7KX10 RCBO, 2P, 10 A, C-curve, 30 mA

MPN 5SU1324-7KX10
Active

Siemens SENTRON 5SU1324-7KX10, RCBO, 2-pole, 10 A rated, C-curve, type A residual current 30 mA, 10 kA (EN 60898) / 20 kA (IEC 60947-2), 110/120 V AC, halogen-free.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SU1324-7KX10 specifications
ParameterValue
Poles2
Depth77 mm
Width54 mm
Height90 mm
Energy limitation class3

Product details

What this RCBO is and what it protects

The Siemens SENTRON 5SU1324-7KX10 is a 2-pole RCBO — a combined residual-current device (type A, 30 mA trip) and miniature circuit breaker (C-curve, 10 A) in one 3-module-width (54 mm) package. It mounts on DIN rail in any orientation and accepts supply from top or bottom. The 10 kA breaking capacity per EN 60898 covers residential and commercial branch circuits; the 20 kA rating per IEC 60947-2 means it can also handle industrial fault levels where the prospective short-circuit current is higher. The C-curve (5–10× In) is the standard choice for mixed resistive and moderate inductive loads — lighting, small motors, general socket outlets — where nuisance tripping from inrush is unlikely.

Key ratings — what they mean for the panel

Rated operational voltage is 110/120 V AC, 50/60 Hz. The insulation voltage (Ui) is 264 V, and overvoltage category III with pollution degree 2 means it's rated for fixed installation downstream of the main distribution board — not for outdoor or wet locations. Surge voltage resistance is 4 kV, adequate for standard transient protection in residential and light commercial panels. The 30 mA type A residual-current element detects pulsating DC fault currents (typical from rectified loads like electronics or LED drivers) as well as sinusoidal AC faults. Mechanical service life is 10 000 operating cycles, which is typical for a panel-protection device — not a switching contactor.

Mounting and integration

The 5SU1324-7KX10 occupies 3 modular width units (54 mm) on a DIN rail. Installation depth is 70 mm; overall depth with terminals is 77 mm. IP20 rating applies only when installed in a distribution board with connected conductors — the device itself is not sealed against dust ingress. Halogen-free and silicon-free construction matters for panels in environments with sensitive electronics or where low-smoke, zero-halogen cabling is specified. Ambient temperature range is -40 °C to 75 °C, which covers most indoor panel environments including unheated enclosures.