Skip to main content
Siemens 5SU1354-6GV10

Siemens 5SU1354-6GV10 SENTRON RCBO, 10 A B-Curve, 30 mA Type

MPN 5SU1354-6GV10
Active

Siemens SENTRON 5SU1354-6GV10 RCBO, 2-pole (1P+N), 10 A B-curve MCB with 30 mA Type A RCD, 10 kA IEC 60898 / 20 kA IEC 60947-2, 2 MW units, IP20.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SU1354-6GV10 specifications
ParameterValue
Poles2
Depth77 mm
Width36 mm
Height90 mm
Energy limitation class3

Product details

The MCB side is B-curve (trips at 3–5× rated current), rated 10 A at 30 °C, and carries a 10 kA breaking capacity per EN 60898 and 20 kA per IEC 60947-2 — the higher figure applies when the device is used in an industrial distribution board where the prospective fault current is known to be higher. The RCD side is Type A, sensitive to sinusoidal AC and pulsating DC residual currents up to 30 mA, which covers the standard shock-protection threshold for personnel in most commercial and light-industrial installations. Thermal derating is published: at 40 °C the continuous rating drops to 9.5 A, at 50 °C to 9 A, and at 70 °C to 8 A — factor this into the panel thermal budget if the RCBO sits in a crowded enclosure.

Panel integration

Snap-on DIN-rail mount, any position. Depth is 77 mm, width 36 mm (2 MW), height 90 mm.

MPN
5SU1354-6GV10