Skip to main content
Siemens 5SU9304-1KK16

Siemens 5SU9304-1KK16 SENTRON RCBO, 16 A, 30 mA, 10 kA

MPN 5SU9304-1KK16
Active

Siemens SENTRON 5SU9304-1KK16 RCBO, 1P+N, 16 A, 30 mA residual current, type C, 10 kA, 1 MW, IP20.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SU9304-1KK16 specifications
ParameterValue
Poles2
Depth77 mm
Width18 mm
Height125 mm
Energy limitation class3

Product details

At higher panel temperatures the current must be derated: 15.04 A at 40 °C, 14.56 A at 45 °C, 13.92 A at 50 °C, and 12.96 A at 55 °C. If your panel runs hot, size the load accordingly or you'll nuisance-trip on the thermal element. The 30 mA residual-current trip is the standard for personal protection in most residential and commercial circuits. If your load includes VFDs, UPS gear, or LED drivers that can generate DC fault components, you need a type A or F RCBO instead. The design is instantaneous (no intentional time delay on the residual element), so it trips fast on a ground fault.

Installed depth is 77 mm, overall height 125 mm. Keep it inside a dry enclosure. The part also carries energy limitation class 3, meaning it limits let-through energy well enough to coordinate with downstream equipment in most cases.

MPN
5SU9304-1KK16