Skip to main content
Siemens 5SV1616-1KK02

Siemens 5SV1616-1KK02 SENTRON RCBO, 2 A C-curve, 300 mA, 6 k

MPN 5SV1616-1KK02
Active

Siemens SENTRON 5SV1616-1KK02 RCBO, 2 A rated, C-curve trip characteristic, 300 mA AC-type residual current, 6 kA breaking capacity per EN 60898, 1 MW wide, IP20.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SV1616-1KK02 specifications
ParameterValue
Poles2
Depth77 mm
Width18 mm
Height90 mm
Energy limitation class3

Product details

What this RCBO does in a panel

The Siemens 5SV1616-1KK02 is a 2-pole (1P+N) SENTRON RCBO — a combined miniature circuit breaker and residual-current device in one 18 mm wide module.

Temperature derating and mounting

Above that, derate linearly: 1.9 A at 40 °C, 1.8 A at 50 °C, 1.7 A at 60 °C, and 1.6 A at 70 °C. IP20 rating applies when installed with conductors connected — the panel door provides the environmental seal.

Halogen-free and silicon-free construction. Energy limitation class 3. The AC-type residual current detection covers sinusoidal fault currents only — not pulsed DC or smooth DC. Operating frequency is 50 Hz; not rated for 60 Hz networks. Supply connection from either top or bottom.

MPN