What this RCBO does in a panel
The Siemens 5SV1616-1KK02 is a 2-pole (1P+N) SENTRON RCBO — a combined miniature circuit breaker and residual-current device in one 18 mm wide module.
Temperature derating and mounting
Above that, derate linearly: 1.9 A at 40 °C, 1.8 A at 50 °C, 1.7 A at 60 °C, and 1.6 A at 70 °C. IP20 rating applies when installed with conductors connected — the panel door provides the environmental seal.
Halogen-free and silicon-free construction. Energy limitation class 3. The AC-type residual current detection covers sinusoidal fault currents only — not pulsed DC or smooth DC. Operating frequency is 50 Hz; not rated for 60 Hz networks. Supply connection from either top or bottom.