Siemens SENTRON 5SV3342-4KK14 RCCB, 4P, 25 A, 30 mA, Type B+

MPN 5SV3342-4KK14
Active

Siemens SENTRON RCCB, 4-pole, Type B+, short-time delayed, In: 25 A, 30 mA, Un AC: 400 V, 10 kA SCCR, DIN rail mount, IP20.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SV3342-4KK14 specifications
ParameterValue
Short circuit rating10 kA
Poles4
MountingDIN rail (REG)
Depth70 mm
Width72 mm
Height90 mm
Grid spacing60 mm

Product details

Type B+ and short-time delayed — what that means for your circuit

Type B+ RCCBs detect AC, pulsating DC, smooth DC, and high-frequency residual currents — the + suffix adds immunity to nuisance tripping from 50/60 Hz line-frequency leakage that can occur in circuits with VFDs, UPS systems, or EV chargers. The short-time delayed design (IEC 61008-1 rated 0.8 kA) introduces a deliberate trip delay, giving downstream MCBs or fuses time to clear a fault first. This selectivity is critical in multi-level distribution where you want the branch breaker to open, not the main RCCB.

Panel integration and environmental limits

Silicon-free construction suits environments where silicone outgassing can contaminate contacts or optics. Overvoltage Category III means it is rated for fixed-installation distribution level, not for downstream equipment-level protection.

Power loss and supplementary devices

Supply voltage for the test circuit is 70 V minimum, with the supply cord position at top or bottom (top preferred for SIGRES function to remain active in switched-off state).