Skip to main content
Siemens 5SV3357-6

Siemens SENTRON 5SV3357-6 RCCB, 4P, 80A, 30mA, Type A

MPN 5SV3357-6
Active

Siemens SENTRON series, RCCB (Residual Current Circuit Breaker), 4-pole, 80 A rated, 30 mA trip, Type A, instantaneous, DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SV3357-6 specifications
ParameterValue
Short circuit rating10 kA
Poles4
MountingDIN rail (REG)
Depth70 mm
Width72 mm
Height90 mm

Product details

That 30 mA trip is the standard for personnel protection in most IEC-based residential and light commercial panels; Type A means it catches pulsating DC faults on top of sinusoidal AC, which covers modern electronics and single-phase rectified loads. The instantaneous design (no intentional delay) clears fast on a fault, but it also means no selectivity against downstream RCCBs — every device on the same circuit sees the fault at the same time.

Snaps onto standard DIN rail (REG profile). Occupies 4 modular width units — that's 72 mm of rail space, so it eats four 18 mm slots in a typical distribution board. Depth is 70 mm, which matches the standard 70 mm installation depth for this class; the height is 90 mm. Mounting position is unrestricted — horizontal, vertical, upside-down, the trip mechanism works the same. Supply can land on top or bottom terminals; no polarity restriction. IP20 with conductors connected and the board closed — that's the usual for enclosed distribution gear, not for open-panel washdown zones.

Thermal derating — the real-world current

At 45 °C it drops to 77.57 A; at 50 °C to 74.59 A; at 55 °C to 70.22 A; at 60 °C to 64.47 A; at 65 °C to 57.35 A; at 70 °C to 48.8 A.

Fault ratings and coordination

Short-circuit current rating (SCCR) is 10 kA per IEC 61008-1. The let-through energy (I²t) is rated at 110,000 A²·s — that's the energy the device lets pass before it clears. Surge current resistance is 1 kA (8/20 μs waveform), which means it survives lightning-induced or switching surges up to that peak without nuisance tripping.

MPN
5SV3357-6