Siemens SENTRON 5SY4208-7KK11 MCB, 2P, C-curve, 8 A, 10/20 k

MPN 5SY4208-7KK11

Siemens SENTRON miniature circuit breaker, 5SY4208-7KK11, 2-pole, C characteristic, 8 A rated, 10 kA (EN 60898) / 20 kA (IEC 60947-2) breaking capacity, 2 MW units, IP20.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SY4208-7KK11 specifications
ParameterValue
Poles2
IP ratingIP20
MountingQuick assembly system
Temp operating max75 °C
Temp operating min55 °C
Depth76 mm
Width36 mm
Height90 mm
Energy limitation class3

Product details

Thermal derating — the number that matters for real loads

The 8 A rating holds only up to 35 °C ambient. Above that, the bimetal strip heats faster and the breaker must derate to avoid nuisance tripping: 7.51 A at 40 °C, 7.26 A at 45 °C, 6.99 A at 50 °C, 6.72 A at 55 °C, and 6.43 A at 60 °C. If your panel internal temperature runs 50 °C, size the load at 7 A max, not 8 A.