Siemens SENTRON 5SY4208-7KK11 MCB, 2P, C-curve, 8 A, 10/20 k

MPN5SY4208-7KK11

Siemens SENTRON miniature circuit breaker, 5SY4208-7KK11, 2-pole, C characteristic, 8 A rated, 10 kA (EN 60898) / 20 kA (IEC 60947-2) breaking capacity, 2 MW units, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY4208-7KK11 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentMechanical engineering / industry
5SY4208-7KK11 — Electrical
ParameterValue
Number of poles2
5SY4208-7KK11 — Protection
ParameterValue
Tripping characteristic classC
Overvoltage categoryIII
5SY4208-7KK11 — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SY4208-7KK11 — Environmental
ParameterValue
Pollution degree3
5SY4208-7KK11 — Specifications
ParameterValue
Energy Limitation Class3

Product details

Thermal derating — the number that matters for real loads

The 8 A rating holds only up to 35 °C ambient. Above that, the bimetal strip heats faster and the breaker must derate to avoid nuisance tripping: 7.51 A at 40 °C, 7.26 A at 45 °C, 6.99 A at 50 °C, 6.72 A at 55 °C, and 6.43 A at 60 °C. If your panel internal temperature runs 50 °C, size the load at 7 A max, not 8 A.