Skip to main content
Siemens 5SY6103-6CC

Siemens 5SY6103-6CC SENTRON MCB, 1P B-Char 3A, 6kA

MPN 5SY6103-6CC

Siemens SENTRON 5SY6103-6CC, 1-pole miniature circuit breaker, B characteristic, 3 A rated current, 6 kA breaking capacity per EN 60898, 18 mm wide.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SY6103-6CC specifications
ParameterValue
Poles1
IP ratingIP20
MountingQuick assembly system
Temp operating max75 °C
Temp operating min55 °C
Depth76 mm
Width18 mm
Height90 mm
Energy limitation class3

Product details

Siemens 5SY6103-6CC — 1-pole B-curve MCB, 3 A, 6 kA

The Siemens SENTRON 5SY6103-6CC is a 1-pole miniature circuit breaker (MCB) with a B tripping characteristic, rated 3 A at 50/60 Hz. It breaks fault currents up to 6 kA per EN 60898 and 5 kA per UL 1077 / CSA C22.2 No.235.

B-curve trip and thermal derating

The 3 A rating holds at 35 °C ambient; at 40 °C it derates to 2.76 A, at 50 °C to 2.49 A, and at 55 °C to 2.34 A. If the panel runs hot (enclosed DIN rail, poor airflow), size up one step or account for the derated figure in the load calculation.

Occupies 1 modular unit (18 mm width) on standard DIN rail. The quick-assembly fastening system snaps onto the rail without tools; mounting position is any. Sealable terminals (top and bottom combined) let the panel builder lock the cover after commissioning — useful for utility-metering or tamper-evident enclosures.

Listed as current production (active lifecycle stage). Halogen-free and silicon-free construction, which matters for clean-room or semiconductor-adjacent panels where outgassing contaminates optics or contacts.

MPN
5SY6103-6CC