Skip to main content
Siemens 5SY6103-6CC — 1-Pole MCB (DIN Rail)

Siemens 5SY6103-6CC SENTRON MCB, 1P B-Char 3A, 6kA

MPN5SY6103-6CC

Siemens SENTRON 5SY6103-6CC, 1-pole miniature circuit breaker, B characteristic, 3 A rated current, 6 kA breaking capacity per EN 60898, 18 mm wide.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY6103-6CC — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Application suitabilityMechanical engineering / industry
5SY6103-6CC — Electrical & Protection
ParameterValue
Tripping characteristic classB
Rated value (EN 60898)6 kA
Energy limitation class3
Overvoltage categoryIII
5SY6103-6CC — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY6103-6CC — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

Siemens 5SY6103-6CC — 1-pole B-curve MCB, 3 A, 6 kA

The Siemens SENTRON 5SY6103-6CC is a 1-pole miniature circuit breaker (MCB) with a B tripping characteristic, rated 3 A at 50/60 Hz. It breaks fault currents up to 6 kA per EN 60898 and 5 kA per UL 1077 / CSA C22.2 No.235.

B-curve trip and thermal derating

The 3 A rating holds at 35 °C ambient; at 40 °C it derates to 2.76 A, at 50 °C to 2.49 A, and at 55 °C to 2.34 A. If the panel runs hot (enclosed DIN rail, poor airflow), size up one step or account for the derated figure in the load calculation.

Occupies 1 modular unit (18 mm width) on standard DIN rail. The quick-assembly fastening system snaps onto the rail without tools; mounting position is any. Sealable terminals (top and bottom combined) let the panel builder lock the cover after commissioning — useful for utility-metering or tamper-evident enclosures.

Listed as current production (active lifecycle stage). Halogen-free and silicon-free construction, which matters for clean-room or semiconductor-adjacent panels where outgassing contaminates optics or contacts.

Frequently asked questions

Where can I buy 5SY6103-6CC and how do I get a price?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit a request with your quantity and target delivery window.

Will 5SY6103-6CC drop into a panel specified around 5SY4116-6CC without rewiring?

Both are 1-pole SENTRON MCBs on the same 18 mm DIN-rail footprint, so the mechanical swap is direct. The electrical difference is the rating: 5SY6103-6CC is 3 A B-curve; 5SY4116-6CC is 16 A B-curve. Verify the load current and the upstream protective device before substituting — the 3 A unit will trip on a 16 A load.

What is 5SY6103-6CC's depth?

Depth is 76 mm (installation depth 70 mm).

What compliance documentation does Siemens provide for 5SY6103-6CC?

The part carries UL 1077 and CSA C22.2 No.235 recognition (5 kA), plus EN 60898 certification (6 kA). It is halogen-free and silicon-free. Full RoHS and REACH declarations are available from Siemens upon request.

MPN
5SY6103-6CC